+44 (0)1392 64 00 20
APC
Galaxy VS UPS 100kW 400V for External Batteries, Halogen-Free Cables, Marine Certified, Start-Up 5x8

Galaxy VS UPS 100kW 400V for External Batteries, Halogen-Free Cables, Marine Certified, Start-Up 5x8

Part Number:
GVSUPS100KMHS
Language:
IN

£15,122.97  (Excl VAT)

Introduction

Highly efficient, easy-to-deploy 100kW, 400V 3-phase UPS. Brings best-in-class power protection and low total cost of ownership to edge, small, and medium data centers, as well as critical infrastructure in commercial and industrial applications. Includes 5x8 start-up service and halogen-free cables. Marine certified.

Specifications

Main

  • Main Input Voltage : 400 V 3 phases
  • Other Input Voltage :
    • 380 V
    • 415 V
  • Main Output Voltage :400 V 3 phases
  • rated power in W : 100 kW
  • rated power in VA : 100 kVA
  • battery type
  • External battery system : Li-Ion (Lithium-Ion)
    VRLA
  • provided equipment :
    • Dust filter
    • EcoStruxure IT ready (UPS)
    • Installation guide
    • Integrated network management
    • Power modules ship installed
    • Start-up service

General

  • bypass voltage tolerance : +/- 10 %
  • redundant : No

Physical

  • colour : White
  • height : 148.5 cm
  • width : 52.1 mm
  • depth : 84.7 cm
  • net weight : 250 kg
  • USB compatible : No

Input

  • network frequency : 40...70 Hz
  • input voltage limits : 340...460 V 400 V
  • maximum input current : 180 A
  • max short time withstand current : 65 kA
  • input harmonic distortion : Less than 3 % for full load
  • load power factor : From 0.7 leading to 0.7 lagging without any derating

Output

  • Maximum configurable power in W : 50 kW
  • output frequency
    • 50 Hz sync to mains
    • 60 Hz sync to mains
    • 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
    • 60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised
  • crest factor :2.5
  • Wave type : Sine wave
  • output voltage tolerance :+/-1% after 50ms
  • output harmonic distortion : < 1% linear load and < 5% non-linear load
  • output overload operation : 10 minutes at 125% and 60 seconds at 150%
  • bypass type : Built-in static bypass
  • Maximum configurable power in VA : 100 kVA

Conformance

  • standards
    • EN/IEC 62040-1
    • EN/IEC 62040-2
    • FCC part 15 class A
    • IEC 60721-4-2 level 2M2
    • UL 1778 5th edition

Environmental

  • ambient air temperature for operation : 0…40 °C
  • relative humidity : 0…95 % non-condensing
  • operating altitude : 0...3300 ft
  • ambient air temperature for storage : -25…55 °C
  • storage Relative Humidity : 10…80 % Non-condensing
  • acoustic level : 68 dBA
  • heat dissipation : 5804 Btu/h
  • IP degree of protection : IP21

Batteries & Runtime

  • battery voltage : 480...576 V DC
  • discharge battery voltage : 384 V DC
  • max current discharge : 271 A
  • Battery power in VAH : 0 VAh runtime
  • extended runtime :0

Communications & Management

  • control panel: Touch screen LCD user interface
  • alarm : Audible and visible alarms prioritized by severity

 

No options for this product
.